This Carbon-free anti-static Veneer has permanent anti-static functionbecause it uses conductive statc network formed
at the inter face of plastic particles.
| Test Items | Standard | Volume Result |
| Thickness | ISO24346-EN430 / SJ/T11236-2001 | 2.0mm |
| Dimensions | ISO 24341-EN426 / SJ/T11236-2001 | 2m x 20m |
| Weight | ISO24341-EN426 / SJ/T11236-2001 | 2850g~3300g/m² |
| System resistance | DIN 51953 / SJ/T11236-2001 | Static Dissipative 1.0x10⁶~1.0x10⁹Ω Conductive 1.0x10⁴~1.0x10⁶Ω |
| Decay period of static voltage | SJ/T10694-2006 | ≤0.4s |
| Staring voltage | SJ/T11236-2001 | |V|<100V |
| Amount of wear | SJ/T11236-2001 | ≤0.02g/cm² |
| Combustion property | GB8624-2006 / SJ/T11236-2001 | Bf1-S1,t1FV-0 |
| Smoke production | GB8624-2006 | ≤750%·min |
| Smoke toxicity | GB8624-2006 | ZA₂ |
| Anti-bacterial | ISO 22196 | 1 Anti bacterial rate 1 |
| Slip resistance | DIN 51130 / EN13893 | R9≥0.3 |
| Toxic testing | GB18586-2001 | Suitable |
| Formaldehyde emission | EN717-1 | N, D |
| Residual indentation | EN433 | ≤0.10mm |
| Effect of castor chair | EN425 | No delamination no cracks |
| Dimensional stability | EN434 | ≤0.40% |
| Color fastness | EN ISO 105-B02 | ≥6 |
| Impact sound absorption | EN ISO 0717/2 | Apprpx 2dB |
| Resistance to staining | EN423:2001 | :0-Not affected |
Carbon-free anti-static Veneers are widely applied to Electronics, microelectronics, tel-ecommunications, network floor clean room, com-puter room, computer room and other precision in-strument and, room for equipment operation.
The Carbon-free anti-static Veneer have been tested before out of the factore, in compliance with quality standards.
Huahong can also provide technical guidance or support in the job site
Within 1 year from purchase, no product defects in the materials and technology, Compliance with regulations for the installation and maintenance, there is 10 years guarantee(except for human reasons and install by buyerselves)
Above guarantee replace anv other assurances. including, but not limited to, any garantee implied in the business feasibility or special purposes.



Because floor is unpermeable, the surface dirty is easy to clean.
Avoid sharp scratches on the floor by hard object,and maintain a surface.
Clearing the floor by neutral detergent, dry after washing then coated with antistatic wax.
Serious dirty or spots can be used to clean the floor cleaning machine